MidNite Solar 300VAC Surge Protector Device - MNSPD300AC
 
Price $119.00
Quantity
Email to a Friend
The MidNite MNSPD300AC is a great replacement for Delta arrestors that have been the mainstay of the industry for many years. The MidNite surge protectors are designed to clamp surge voltage to safe levels for sensitive electronics.

The MidNite Solar Surge Protector Device (MNSPD) is a Type 2 device per UL1449 rev3. It is designed for both AC and DC systems and provides protection to service panels, load centers or where the SPD is directly connected to the electronic device requiring protection.

Listed by ETL for US & Canada





Selecting the Proper Voltage Surge Protector:

The MidNite Solar SPD is offered in three different voltages to maximize the required protection level. Protection is achieved by reducing the clamping voltage to a safe voltage that your system can sustain without damaging any electronics in the system. By using the chart below select the SPD’s that provide the protection your system requires. If you have questions or need assistance selecting the correct unit don't hesitate to contact us.

Midnite Solar Surge Protection Selection Table
Part No. 
MNSPD115 
MNSPD300AC and
MNSPD300DC 
MNSPD600 
Nominal Voltage   0 to 90 VAC
0 to 115 VDC 
0 to 250 VAC (AC model)
0 to 300 VDC (DC model)  
0 to 485 VAC
0 to 600 VDC 
MCOV
VRMS @1mA  
180V (162-198)  470V (423-517)  780V (702-858) 
ClampV @ 100A
Current 8/20µs 
295V  775V  1290V 
I peak (8/20µs)
(Current) 
100kA (Full Device)
50kA (Each Section) 
100kA (Full Device)
50kA (Each Section) 
100kA (Full Device)
50kA (Each Section) 
Energy Absorption  1120 J (Full Device)
560 J (Each Section) 
3130 J (Full Device)
1560 J (Each Section) 
4320 J (Full Device)
2160 J (Each Section) 
Suggested  Placement  Up to 90 VAC circuits, 12V,24V,48V DC battery circuits 120/240VAC circuits, offgrid PV combiners and charge controller inputs up to 300VDC 316V/480VAC circuits Grid tie PV combiners Grid tie inverter input 


Features:

Diagnostics  SPD300AC -LED indicators when voltage is present between L1+Ground and L2+ground SPD115, 300DC and 600- LED Indicators when voltage is present between DC+ and DC- 
Operating Temperature Range  -40°c to +85°c  
Nominal Discharge Current    20kA 
Thermal Disconnector Internal  Internal 
Response time  <15n sec. 